Super Super

Fire truck water pressure per floor

Elevation & friction model

Available nozzle pressure by floor

Modeled from pump, friction, elevation and appliance losses
Available nozzle pressure by floor Line chart of available nozzle pressure at each floor, with the nozzle target as a dashed reference line.
Available pressure Nozzle target Below target

How the per-floor pressure model works

Fireground pump pressure is not the pressure that reaches the nozzle. Between the pump and the nozzle you lose pressure to friction in the hose, to lifting water up the building, and to appliances such as wyes, standpipe connections and manifolds. This calculator applies those losses floor by floor so you can see where the nozzle pressure falls below the target.

The equation used

Available = Pump − Friction − (0.434 × floorHeight × floor) − Appliance

Elevation loss uses the standard 0.434 psi per foot of lift (roughly 4.34 psi per 10-ft floor). Friction loss uses the fire-service coefficient method:

FL = C × (Q / 100)² × (L / 100)

where C is the hose coefficient, Q is flow in gpm, and L is hose length in feet. Coefficients used here are the commonly published values for each hose size:

These coefficients are approximations. Actual friction loss varies with hose construction, coupling type, water temperature and gasket condition. Treat the output as a planning estimate, not a substitute for a pump chart, a flow test, or your department's SOPs.

Reading the result

The chart plots available pressure at each floor up to the number you entered. The dashed line is your nozzle target. Any floor whose available pressure falls below the target is marked in red — that floor is beyond the reach of the current pump setting, hose layout and appliance losses. The "highest reachable floor" figure is the last floor at or above the target.

What this model does not include

Why does elevation cost about 0.434 psi per foot?

One foot of water column equals about 0.434 psi. Lifting water 10 feet therefore costs roughly 4.34 psi regardless of hose size or flow — it is a static head loss, not a friction loss.

Should I use the 1¾ or 2½ coefficient for a standpipe?

Use the coefficient that matches the hose actually deployed from the standpipe outlet to the nozzle. If the building's standpipe supplies a 2½ in line, use the 2½ coefficient even if the pump is feeding a larger supply line below.

How do I account for a wye or manifold?

Add the appliance loss for the wye or manifold to the "Appliance loss" field. If two attack lines are flowing, enter the combined flow and the appliance loss for the manifold; the model treats the layout as a single line.

Is this a substitute for a pump chart?

No. It is a planning aid for understanding how pump pressure, friction, elevation and appliance losses interact. Always follow your department's pump charts, SOPs and pump operator training.